Skip to guide
Guide / DGU glass

DGU Load Sharing Guide for Structural Glazing

An insulated glass unit does not always put the full external action into one pane. VitraLab reviews DGU glass as a pane-and-cavity system so load sharing between the outer and inner panes can be considered in stress and deflection checks.

DGU glass Insulated glass unit Load sharing

DGU load-sharing concept External action and cavity-pressure transfer DGU
01 / 06

Overview

Primary topic
DGU glass
Engineering basis
Insulated glass unit
Review status
Project-specific verification required

Why DGU Load Sharing Matters

In a DGU, the cavity links the panes through pressure change. Under wind pressure or suction, part of the action may be carried by the directly loaded pane and part may be transferred to the opposite pane depending on pane stiffness and cavity behavior.

Outer Pane and Inner Pane Results

A useful DGU review should identify which pane is being checked and show pane-level stress and deflection output. The governing pane may change between pressure, suction, ULS stress, and SLS deflection cases.

02 / 06

Load Sharing

Effect of Laminated Panes

If one pane is laminated and the other pane is monolithic, their stiffness can be very different. VitraLab uses the relevant laminated-glass equivalent thickness for that pane rather than treating both panes as identical.

Wind Pressure and Wind Suction

Positive and negative wind actions can produce different pane effects. The outer pane and inner pane should both be reviewed because suction, pressure, and transferred cavity effects can govern different checks.

03 / 06

Engineering Review

DGU Engineering Basis

This guide explains the load-sharing concept so engineers can understand why the outer and inner panes require separate stress and deflection review. The related glass deflection calculator page explains the serviceability inputs and outputs in more detail.

Engineering Review

Review pane dimensions, cavity thickness, outer and inner pane build-ups, support condition, wind actions, ULS stress, SLS deflection and output warnings. The calculation remains project-specific and does not replace review of the complete insulating-glass system and its supports.

Example Configuration and Load Basis

The worked example uses a vertical 1000 × 2000 mm four-edge supported 10 / 16 / 10 DGU. Both panes are 10 mm annealed monolithic glass, the reference cavity state is 101.325 kPa at 20 °C, and the applied 3 s wind actions are +0.750 kN/m² pressure and −0.500 kN/m² suction.

Example Pane-Pressure Distribution

For positive wind, the cavity pressure increases by 0.338 kPa and the resulting pane pressure components are +0.412 kN/m² on Pane 1 and +0.338 kN/m² on Pane 2. For suction, the cavity-pressure variation is −0.225 kPa and the pane components are −0.275 kN/m² and −0.225 kN/m² respectively.

Example Governing Result and Interpretation

Pane 1 governs both limit states for this input set. The governing ULS case has 3.714 N/mm² stress and 0.149 utilization. The governing SLS case has 0.676 mm deflection against a 15.385 mm limit, giving a ratio of 0.044. Different pane stiffnesses, cavity dimensions, reference states or actions can change the distribution and governing pane.

04 / 06

Worked Example: DGU 10 / 16 / 10

The calculation uses the implemented rectangular-IGU route from the reviewed 2024 prEN 19100-2 draft.

Pane size
1000 × 2000 mm
Orientation and support
Vertical, four edges supported
DGU build-up
10 / 16 / 10
Glass panes
10 mm annealed monolithic glass
Reference cavity state
101.325 kPa at 20 °C
Applied wind actions
+0.750 / −0.500 kN/m², 3 s duration
ULS PASS
Governing combination
1.5 Wind
Design action
1.125 kN/m²
Calculated response
3.714 N/mm² stress, Pane 1
Utilization or ratio
0.149 utilization
SLS PASS
Governing combination
Wind
Design action
0.750 kN/m²
Calculated response
0.676 mm deflection, Pane 1
Utilization or ratio
0.044 of 15.385 mm limit

For +0.750 kN/m² wind, the pane pressure components are +0.412 kN/m² on Pane 1 and +0.338 kN/m² on Pane 2. For −0.500 kN/m² suction, they are −0.275 kN/m² and −0.225 kN/m² respectively. Pane 1 governs this input set. Open the EC10 calculator to reproduce or change the inputs.

05 / 06

DGU Engineering Figures

Swipe horizontally to view more figures

DGU load-sharing concept showing two glass panes, one sealed cavity, external action and cavity-pressure transfer
Conceptual DGU load sharing through calculated cavity-pressure change.
DGU glass load diagram for vertical four-edge supported structural glazing
Example load application for vertical four-edge supported DGU glazing.
DGU pane-specific stress response for vertical four-edge supported structural glazing
Example pane-specific stress response for vertical four-edge supported DGU glazing.
DGU pane-specific SLS deflection response for vertical four-edge supported structural glazing
Example pane-specific SLS deflection response for vertical four-edge supported DGU glazing.
06 / 06

Frequently Asked Questions

Does a DGU put all wind load on the outer pane?

Not necessarily. DGU behavior depends on pane stiffness and cavity interaction, so both panes should be reviewed.

Can the inner pane govern a DGU check?

Yes. Depending on stiffness, build-up, pressure or suction direction, and limit state, either the outer pane or inner pane may govern.

Does laminated glass affect DGU load sharing?

Yes. A laminated pane may have different effective stiffness from a monolithic pane, which can affect load sharing and pane-level results.

Should DGU stress and deflection be checked separately?

Yes. ULS stress and SLS deflection are separate checks, and the governing pane or action can differ between them.

Engineering content is prepared and maintained by VitraLab Engineering. Worked examples record the current calculator workflow and do not replace project-specific verification.